1 Kv Pin Insulator
Following are the Standard Particular of 11 KV Pin Insulator(SC-PN-1102)
| Drawing No. | KV | SC-PN 1102 |
| Highest System Voltage | kV | 12 |
| Working Voltage | kV | 11 |
| Creepage Distance Minimum | mm | 280 |
| Visible Discharge Voltage | kV | 9 |
| Mechanical Failing Load | KN | 10 |
| Power Frequency Withstand Voltage |
|
|
| Wet | kV | 35 |
| Dry | kV | 15 |
Additional Information:

Price: